MEDIUM PRESSURE CENTRIFUGAL FAN WITH FORWARD IMPELLER
MANUFACTURING FEATURES:
• Rolling steel sheet housing.
• Completely joined or welded housing.
• Galvanised steel sheet simple inlet forward curved impeller.
• Polyester powder finishing coat.
• Standard asynchronous squirrel-cage motor with IP-55 protection and Class F insulation. Manufactured with standard voltages: 230V 50Hz in single phase motors and 230/400V 50Hz in three phase motors.
• Available positions (to be indicated in case of order): LG270, LG0, LG45, LG90, LG135, LG180, LG225, LG315, RD0, RD45, RD90, RD135, RD180, RD225, RD270, RD315.
• The indicated codes correspond to the model in position LG270
APPLICATIONS:
Designed for inline installation, they are suitable for:
• Industrial applications, extraction or injection of air.
• Cooling of machines and parts.
• Suitable for transporting totally clean air without dust.
• Maximum working temperature: carried air: 130ºC, environment single phase 50ºC, three phase 60ºC.
UNDER REQUEST:
• Special voltages.
• 2 speed motors (three phase motors).
•Fan for air working temperatures up to 250ºC.
• Fans provided with cooling disk for high temperature.
• Option with support for models where it is not included, and without support for models where it is included.
A | B | C | D | E | F | G | H | K | N | O | P | Q | S | TØ | UØ | VØ | Y |
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
365 | 321 | 139 | 141,5 | 213 | 115 | 141,5 | 360 | 214 | 169 | 146 | 169 | 237 | 192 | 9 | 143 | 9 | 4x90º |
MANUFACTURING FEATURES
• For axial (inlet and outlet) and centrifugal (inlet) fans.
UNDER REQUEST
• Versions in stainless 304 and stainless 316.